Please use this identifier to cite or link to this item: http://repositorio.lnec.pt:8080/jspui/handle/123456789/16605
Title: The use of impulse ventilation to control pollution in underground car parks
Authors: Viegas, J.
Keywords: Impulse ventilation;Underground car park;Jet fan;Cfd
Issue Date: Jun-2009
Publisher: VEETECH Ltd.
Abstract: The ventilation of underground car parks is important to avoid health problems with the inhalation of combustion products released by car engines, in special CO (that is commonly used as the indicator of indoor air quality). In last years, a new mechanical ventilation system appeared, based on the use of axial ventilators (jet fans) suspended under the car park ceiling. In this paper the flow generated by jet fans and their effects on the pollutants are studied. It is concluded that jet fans may have a pumping effect entraining the surrounding contaminated air into the jet. In this way jet fans are able to restrict the dispersion of the contaminants, provided that the exhaust flow rate from the car park is not lower than the jet flow rate. Impulse ventilation may also provide fast dilution of the local pollution peaks, but in this case the removal efficiency will be low. This paper also suggests criteria to define the distance between jet fans.
URI: https://repositorio.lnec.pt/jspui/handle/123456789/16605
ISSN: 1473-3315
Appears in Collections:DED/NAICI - Comunicações a congressos e artigos de revista

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.