dc.description.abstractThis paper analyses the possibility of using air curtains to prevent smoke flow from fire compartments. Full size experiments have been carried out and several relevant conditions to assess smoke-tightness have been tested. The smoke temperature during the tests was ranging from 182ºC to 351ºC, the angle measured between the curtain axis and the vertical plane was ranging from 18º and 26º, the nozzle thickness was ranging from 0.017 m to 0.045 m and the velocity at the nozzle was ranging from 8.3 m/s to 19.9 m/s. During the tests, the air curtain’s nozzle was positioned horizontally at the top of a permanent opening (door). With this configuration, we obtained an approximately vertical downward jet through the used opening. This paper includes the final results of the tests and develops an analytical tool for predicting the performance of air curtains. It was concluded that it is possible to achieve smoke-tightness, provided that the adequate plane jet parameters and the compartment’s smoke exhaust are correctly adjusted. According to this analysis, the smoke-tightness limit corresponds to equation B=〖ΔP〗_a⁄〖ΔP〗_s =-0.30 u_a⁄u_(a_min) +1.25 (with 1.30≤ u_a⁄u_(a_min) ≤1.67).pt_BR
dc.language.isoengpt_BR
dc.publisherSpringerpt_BR
dc.relationQREN no. 23226 - Smoke Shieldpt_BR
dc.rightsrestrictedAccesspt_BR
dc.subjectSmoke controlpt_BR
dc.subjectPlane jetspt_BR
dc.subjectFull size experimentspt_BR
dc.subjectVertical air curtainspt_BR
dc.titleAir curtains combined with smoke exhaust for smoke control in case of fire: Full-size experimentspt_BR
dc.typeworkingPaperpt_BR
dc.identifier.localedicaoUnited Statespt_BR
dc.description.pages22ppt_BR
dc.description.sectorCIC/CHEFIApt_BR
dc.description.magazineFire Technologypt_BR
dc.contributor.peer-reviewedSIMpt_BR
dc.contributor.academicresearchersSIMpt_BR
dc.contributor.arquivoNAOpt_BR
Appears in Collections:CICTI/Chefia - Comunicações a congressos e artigos de revista

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.