Please use this identifier to cite or link to this item: http://repositorio.lnec.pt:8080/jspui/handle/123456789/1000359
Full metadata record
DC FieldValueLanguage
dc.contributor.authorAveiro, J.pt_BR
dc.contributor.authorViegas, J.pt_BR
dc.contributor.editorJ. C. Pereira and A. Sequeirapt_BR
dc.date.accessioned2010-07-06T15:12:55Zpt_BR
dc.date.accessioned2014-10-10T09:18:20Zpt_BR
dc.date.accessioned2016-06-21T10:00:33Z-
dc.date.available2010-07-06T15:12:55Zpt_BR
dc.date.available2014-10-10T09:18:20Zpt_BR
dc.date.available2016-06-21T10:00:33Z-
dc.date.issued2010-06-14pt_BR
dc.identifier.urihttps://repositorio.lnec.pt/jspui/handle/123456789/1000359-
dc.description.abstractThe covered car parks need to have means of ventilation, natural or mechanical, that provide the exhaust of the combustion products released by the engines of the vehicles passing through and to control the smoke released by fire. In last years, a new mechanical ventilation system appeared, based on the use of axial ventilators (jet fans) suspended under the car park ceiling. Jet fans generate the momentum necessary to promote the internal ventilation flow. In this way, the inlets and outlets may be concentrated in some points of the underground car park. Due to the general geometry of car parking, the flow can be rather complex, so parameters like the jet fans position, orientation and velocities have to be carefully chosen [1; 2]. While widely accepted design recommendations for this kind of projects are missing, the use of CFD software, as complement and auxiliary tool in the evaluation of ventilation design, can be of great interest. In this context, CFD simulations were carried out, using a freeware code (the FDS - Fire Dynamics Simulator), to evaluate and confirm the performance of an existing ventilation system, installed in an underground car park, in a fire scenario. The CFD results were compared with experimental values.pt_BR
dc.language.isoengpt_BR
dc.rightsrestrictedAccesspt_BR
dc.subjectCfd simulationpt_BR
dc.subjectUnderground car parkpt_BR
dc.subjectImpulse ventilationpt_BR
dc.subjectExperimentspt_BR
dc.titleSmoke control in an underground car park with impulse ventilationpt_BR
dc.typeworkingPaperpt_BR
dc.identifier.localedicaoLisboapt_BR
dc.description.figures18pt_BR
dc.description.pages18ppt_BR
dc.identifier.seminarioECCOMAS CFD 2010pt_BR
dc.identifier.localLisboapt_BR
dc.description.sectorDED/NAICIpt_BR
dc.description.year2010pt_BR
dc.description.data14 a 17 de Junhopt_BR
Appears in Collections:DED/NAICI - Comunicações a congressos e artigos de revista

Files in This Item:
There are no files associated with this item.


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.